3701-31-04 (D)(02) / Public swimming pool is continuously disinfected using a chemical feeding device connected to the circulation system
Critical A trichlor tablet was found inside the skimmer basket at the time of the inspection.
The pool must be continuously disinfected using a chemical feeding device connected to the circulation system.
3701-31-04 (B)(4)(a)(vi) / Total alkalinity is tested weekly
Repeat Total alkalinity was not tested weekly.
Test total alkalinity at least once/week.
3701-31-04 (B)(4)(a)(vii) / Cyanuric acid is tested weekly
Cyanuric acid was not tested weekly. Stabilized trichlor tablet observed in the skimmer basket at the time of the inspection. These tablets add cyanuric acid to the pool.
Since cyanuric acid is being added to the pool, the operator must test and record cyanuric acid level at least once/week.
3701-31-04 (C)(2) / pH is within 7.2 to 7.8
Repeat pH reading (which was significantly less than 6.8 - controller readout was 5.9) was outside the range of 7.2 to 7.8.
Treat the pool water so that the pH is within the acceptable range.
3701-31-04 (C)(3) / Total alkalinity is at or greater than 60 ppm
Repeat Total alkalinity measured at 20 ppm was less than minimum 60 ppm required by code.
Raise the total alkalinity to at least 60 ppm.
[?] Facility Type: Pool
[?] Inspection Type: Standard
[?] Inspection Date: 13-July-2017
Comments |
---|
pH reading listed above is the reading from the ACC for this pool. The pH chemical test result was below the bottom reading of 6.8 in the inspector's test kit. |