No critical violations were documented at the time of inspection.
No violations were documented at the time of inspection.
[?] Facility Type: Add't Pool
[?] Inspection Type: Follow-up
[?] Inspection Date: 18-July-2014
The following violation(s) have been corrected since the last inspection. |
---|
3701-31-04 (C)(2)/pH is within 7.2 to 7.8 The baby pool pH was noted at 6.8. Seven (7) drops of base demand reagent raised the pH to 7.2. Raise and maintain the pH of the baby pool between 7.2-7.8. Correct By: 08-Jul-2014 Ms. Michelson agreed to voluntarily close the pool. pH adjustment chemicals were added. Correct By: 17-Jul-2014 |
3701-31-04 (D)(6)(a)/Pool free chlorine disinfectant residual is above 1 ppm. Pool free chlorine disinfectant residual was noted at 0.6ppm. Raise and maintain the free chlorine level at 1ppm minimum. Correct By: 17-Jul-2014 |
3701-31-04 (D)(7)(c)/Audible/visual alarm when unit is malfunctioning or when pH or ORP levels are not acceptable. The ACC unit auto shut off function could not be determined. Determine a way to test the ACC unit automatic shut off. Correct By: 17-Jul-2014 |
3701-31-04 (B)(6)/Equipment is maintained per manufacturers specifications. The skimmer weir is missing. Replace the missing skimmer weir. Correct By: 17-Jul-2014 |
Comments |
---|
All violations corrected. Thanks! Note: The 7/17/2014 reinspection was rescheduled. Reinspection conducted by Scott Bradley,R.S. 732-7614 |