3701-31-04 (D)(7)(a) / pH and ORP values for chlorine/bromine are continuously monitored.
Critical pH values were noted at 5.8. However when the pool water was tested using reagent # 1003J the pH was noted at 7.9
Have the ACC unit serviced so that the pH values are continuously monitored
3701-31-04 (B)(4)(a)(iv) / Water temperatures are recorded daily
Water temperatures were not being recorded daily.
Take and record the water temperature at least once/day.
3701-31-04 (B)(4)(a)(vi) / Total alkalinity is tested weekly
Total alkalinity was not tested weekly.
Test total alkalinity at least once/week.
3701-31-04 (B)(6)(i) / A means of determining rate-of-flow on all water pumps
A means of determining rate-of-flow was not found for all water pumps.
Properly install a flow meter or have a pump curve available for every water pump used for the pool.
3701-31-04 (B)(6)(s) / Perimeter barrier is in good repair to prevent unauthorized entry
Gate does not slef close and self latch all the time.
Repair the gate.
3701-31-04 (C)(2) / pH is within 7.2 to 7.8
Repeat pH was 7.9
Treat the pool water so that the pH is within the acceptable range (7.2 to 7.9).
3701-31-04 (E)(2)(a)(ii) / A USCG Type IV personal flotation device with 30 -60 foot throw line provided
The throw line of A USCG Type IV personal flotation device was thin.
Provide a proper floatation device with a throw line that is one qaurter of an inch in diameter.
3701-31-04 (E)(2)(d) / First aid kit provided
First aid equipment was not provided.
Provide first aid equipment, including a first aid kit, at the pool at all times.
[?] Facility Type: Add't Pool
[?] Inspection Type: Standard
[?] Inspection Date: 20-August-2014
Comments |
---|
Ole Michelson mentioned that the pool was emptied yesterday for maintenance. Pool water was clear. A reinspection is scheduled on August 25, 2014. |