3701-31-04 (B)(1)(c) / Minimum disinfection residual shall be maintained as required.
Critical Repeat Corrected During Inspection Chlorine disinfectant residual was less than 1 ppm for the pool. Root cause appears to be collapsed or worn out tubing inside the pump housing. Could also be a clogged injector port.
Do not operate the pool when the disinfectant residuals are less than what is required. Ensure the chlorine disinfectant residual is at 1 ppm or above prior to placing the pool back into operation. Julie Michelson was contacted to service the chlorine feed system.
3701-31-04(D)(6)(a)(2) / Pool free chlorine disinfectant residual shall be above 1 ppm.
Critical Repeat Corrected During Inspection Pool free chlorine disinfectant residual was below 1 ppm.
Do not operate the pool until the chlorine disinfectant residual is at 1 ppm or above.
3701-31-04 (C)(2) / pH is within 7.2 to 7.8
Repeat Corrected During Inspection pH was outside the range of 7.2 to 7.8.
Treat the pool water so that the pH is within the acceptable range. Pool tech added acid to the pool water. pH dropped to 7.2 prior to conclusion of inspection.
[?] Facility Type: Pool
[?] Inspection Type: Standard
[?] Inspection Date: 09-August-2018
Comments |
---|
Water clarity meets minimum code requirements at this time. |