3701-31-04 (B)(6) / Equipment is maintained per manufacturers specifications.
The skimmer weir is missing.
Replace the missing skimmer weir. Correct By: 17-Jul-2014
3701-31-04 (C)(2) / pH is within 7.2 to 7.8
The baby pool pH was noted at 6.8. Seven (7) drops of base demand reagent raised the pH to 7.2.
Raise and maintain the pH of the baby pool between 7.2-7.8. Correct By: 08-Jul-2014
Ms. Michelson agreed to voluntarily close the pool. pH adjustment chemicals were added. Correct By: 17-Jul-2014
3701-31-04 (D)(6)(a) / Pool free chlorine disinfectant residual is above 1 ppm.
Pool free chlorine disinfectant residual was noted at 0.6ppm.
Raise and maintain the free chlorine level at 1ppm minimum. Correct By: 17-Jul-2014
3701-31-04 (D)(7)(c) / Audible/visual alarm when unit is malfunctioning or when pH or ORP levels are not acceptable.
The ACC unit auto shut off function could not be determined.
Determine a way to test the ACC unit automatic shut off. Correct By: 17-Jul-2014
[?] Facility Type: Add't Pool
[?] Inspection Type: Standard
[?] Inspection Date: 08-July-2014
Comments |
---|
Pool Notes: 1. Filter pressure gauge noted at 12psi. 2. Turnover rate=0.6 hours. 3. ACC pH noted at 8.08. 4. The pool water was clear Inspection conducted by Scott Bradley,R.S. 732-7614 |