3701-31-04 (B)(6)(t) / Equipment/chemical/storage areas are free of hazards/accessible only to authorized personnel.
Critical Repeat Observed the pool pump room and chemical storage area doors to be propped open and accessible to the public. All equipment, chemical, and other storage areas shall be maintained in a clean condition, free from any hazards, and accessible to authorized personnel only.
Ensure the doors are closed and areas maintained inaccessible to the public.
3701-31-04 (A) / Approval shall be obtained for any construction or alterations of a public swimming pool.
Repeat Observed the chemical disinfection feeder pump to have been replaced with a Mec-O-Matic, Dolphin Series Model No. US50-XA-SAUXXX from a FlexFlow Model No. A1N30A7T.
Ensure an Equipment Replacement Notification form is completed and submitted to the Ohio Department of Health for review and approval.
3701-31-04 (B)(6)(p) / Deck surfaces are free of standing water or other hazards.
Repeat Observed the pool deck to be in disrepair and crumbling by the pool main entry hand rail at the shallow end.
Repair areas of the deck where standing water is occurring. If more than 50% of the deck must be replaced, plans must be submitted to the Ohio Department of Health for review and approval.
3701-31-04 (B)(6)(s) / Perimeter barrier is in good repair to prevent unauthorized entry
Repeat Observed both entry gates of the perimeter barrier not self-closing or latching. All perimeter barriers shall be with gates or doors that are self-closing and lockable.
Repair the gates so they are self-closing and latching.
3701-31-04 (C)(2) / pH is within 7.2 to 7.8
pH was outside the range of 7.2 to 7.8. Observed the pH to be 8.0.
Treat the pool water so that the pH is within the acceptable range.
3701-31-04 (E)(3)(c) / Location of emergency telephone posted when the phone is not visible.
Repeat Sign indicating the location of the emergency device (telephone) was not provided and emergency device was not visible in the pool area.
Ensure that a sign informing patrons of the location of the emergency device is always visible in the pool area.
[?] Facility Type: Pool
[?] Inspection Type: Follow-up
[?] Inspection Date: 07-June-2022
The following violation(s) have been corrected since the last inspection. |
---|
3701-31-04 (B)(1)(a)/Outlet covers shall be installed/secured/in compliance Observed the equalizer lines to be operational and not properly covered with compliant covers. Outlet covers shall be secured at all times so they cannot be removed without the use of tools. Outlet covers shall meet the requirements of ANSI/ASME A112.19.8-2007. Equalizer lines shall have compliant covers or be removed or plugged. Ensure the equalizer lines are properly covered, removed, disabled or plugged. |
3701-31-04 (B)(6)(k)/Outlet drain covers are secure/meet ANSI/ASME A112.19.8-2007 requirements. Observed the equalizer lines to be operational and not properly covered. Outlet covers shall be secured at all times so they cannot be removed without the use of tools. Outlet covers shall meet the requirements of ANSI/ASME A112.8-2007. Equalizer lines shall have compliant covers or be removed or plugged. Was informed the covers are in the equipment storage room. Replace the equalizer line covers to prevent possible injury to bathers and to prevent possible entrapment hazards. |
Comments |
---|
INSPECTION NOTES: --Observed the equalizer lines covers to be securely in place under the skimmer baskets. |