[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (D)(7)(d) / Flow or pressure switch with a shut off valve shall be provided and tested monthly.
Critical Corrected During Inspection Pressure switch for a shut off valve was not tested monthly
Provide records indicating that the unit is being tested monthly.

3701-31-04 (B)(4)(a)(ix) / Chemicals added to the pool other than those used for disinfection
Repeat Chemicals added to the pool other than those used for disinfection were not being recorded.
Facility records must indicate when chemicals, other than disinfectants, are added to the pool water.
3701-31-04 (B)(6)(h) / Required meters and gauges maintained/functional
Repeat The flow meter is not functioning correctly and is not accurately measuring flow.
Repair the flow meter to accurately measure flow.


Inspection Information


[?] Facility Type: Pool

[?] Inspection Type: Standard

[?] Inspection Date: 18-April-2016


Comments
-The disinfectant residuals and water quality parameters meet code requirement.
-Alkalinity was measured at 70 ppm, the ideal range is 80-120 ppm.
-Free Chlorine was measured at 7 ppm, the recommended range is 1-5 ppm.
-All required safety equipment was provided.
-The pool perimeter was secure.
-The filter pressure was 17 psi.
-The pool water was clear.
-The ACC unit measured pH at 7.7.
-Turnover rate was unable to be calculated during the inspection.
If you have any questions or concerns, call me at (513) 732-7612.