3701-31-04 (B)(6)(h) / Required meters and gauges maintained/functional
The pressure gauge on the filter is not functioning properly.
Repair the pressure gauge to ensure it functions properly.
3701-31-04 (E)(2)(d) / First aid kit provided
Repeat Gloves were not provided in the first aid kit.
Provide gloves in the first aid kit.
[?] Facility Type: Pool
[?] Inspection Type: Standard
[?] Inspection Date: 14-June-2016
Comments |
---|
-The disinfectant residuals and water quality parameters meet code requirement. -Free chlorine was measured at 8 ppm, the ideal range is 2-4 ppm. -All required safety equipment was provided. -The pool perimeter was secure. -The filter pressure was unable to be determined. -The pool water is clear. -Turn over rate was 321 minutes. If you have any questions or concerns, call me at (513) 732-7612. |