3701-31-04 (B)(6)(c) / Cross connection hazards shall be prevented.
Repeat Gutter was tied to backwash line from filter.
Remove all cross connection hazards from the pool area.
3701-31-04 (B)(6)(f) / Required turnover rates are sufficient
Repeat Required turnover rates were not met.
Have the circulation system evaluated to determine why the turnover rates are not able to be met. Once the reasons have been determined have the issue repaired. If necessary, submit plans to the Ohio Department of Health to review and approve.
[?] Facility Type: Pool
[?] Inspection Type: Follow-up
[?] Inspection Date: 31-July-2018
The following violation(s) have been corrected since the last inspection. |
---|
3701-31-04 (B)(6)(j)/All SVRS devices are maintained/ functional and tested SVRS device was not tested in accordance with the manufacturer's specifications. Have the SVRS device tested immediately and maintain the test results on site. |
Comments |
---|
According to operator, SVRS system was tested and worked yesterday morning. |