3701-31-04 (B)(6)(h) / Required meters and gauges maintained/functional
Repeat Weirs are missing from the skimmers. Replace the missing weirs.
Maintain all meters and gauges in a properly functioning manner at all times while the pool is in operation.
3701-31-04 (E)(2)(c) / Safety lines provided
Repeat Safety line to mark the change in depth of the pool was not in place or not provided. Provide a Safety Line.
Keep the safety line in place at all times unless it is interfering with lap swimming or other temporary aquatic activities.
[?] Facility Type: Pool
[?] Inspection Type: Standard
[?] Inspection Date: 03-August-2023
Comments |
---|
Pool Notes: 1. The pool water is clear. 2. ACC unit alarlm functioned when tested. ACC and SVRS device testing is documented. 3. ACC unit pH noted at 7.8. 4. The pool turnover rate=8.8 hours. For an 8 hour turnover rate, a flow rate of 132gpm is recommended. 5. Copy of the report was emailed to Ms. Michelson. Contact Scott Bradley,R.E.H.S. (732-7614) with any questions. |