[?] A summary of the violations found during the inspection are listed below.

3701-31-04 ( D )(6)(a) / ORP reading shall be 650 millivolts or greater.
The ACC unit ORP reading was noted at 626mv. Raise and maintain the ACC unit ORP at 650mv minimum.
Have the ACC unit inspected to determined why the ORP is low.
3701-31-04 (B)(6)(q) / Depth markers/deck warning signs are maintained
Repeat The pool depth markers have faded. Repaint the markers so the pool depths are visible.
Replace the depth markers/deck warning signs so that bathers are able to clearly see the depth of the water and that no diving is permitted where clearly indicated.


Inspection Information


[?] Facility Type: Pool

[?] Inspection Type: Standard

[?] Inspection Date: 24-June-2019


Comments
No other violations observed during the inspection.
The pool otherwise looks great!
Pool Notes:
1. The 2019 pool license is posted.
2. The pool water is clear.
3. Proper safety equipment is available for use.
4. ACC unit and SVRS device testing is documented in the pool records.
5. Filter pressure gauges were noted at 10psi.
6. Pool turnover rate=7.5hours.
7. The pool pH was between 7.6-7.8.
8. Main Drain cover information was obtained.
9. The report was emailed to Ms. Michelson.
Inspection conducted by Scott Bradley,R.S. 732-7614