3701-31-04 (B)(1)(c) / Minimum disinfection residual shall be maintained as required.
Critical Repeat Pool chlorine level is less than 1ppm. Observed to be .4ppm
Chlorine should remain above 1ppm.
3701-31-04(D)(6)(a)(2) / Pool free chlorine disinfectant residual shall be above 1 ppm.
Critical Repeat Pool free chlorine disinfectant residual was below 1 ppm.
Do not operate the pool until the chlorine disinfectant residual is at 1 ppm or above.
3701-31-04 ( D )(6)(a) / ORP reading shall be 650 millivolts or greater.
Repeat ORP reading was below 650 mv
Have the ACC unit inspected to determined why the ORP is low.
[?] Facility Type: Pool
[?] Inspection Type: Follow-up
[?] Inspection Date: 11-August-2021
The following violation(s) have been corrected since the last inspection. |
---|
3701-31-04 (C)(2)/pH is within 7.2 to 7.8 pH was outside the range of 7.2 to 7.8. Treat the pool water so that the pH is within the acceptable range. |
Comments |
---|
Pool chlorine remains below .5ppm. A third re-inspection will be conducted. Ensure the wading pool is being tested, if below .5ppm, the pool closed sign should be placed. |