Sampling Details | |||
---|---|---|---|
Sub Type: Other | Special Feature: | Location: | |
Area: 1650 | Volume (gallons): 51000 | Flow measure reading (gpm): 0 | Minimum required flow (gpm): 110 |
Disinfectant: Sodium Hypochlorite | Secondary Disinfectant: | ORP: 760 | Turnover Rate (min): 480 |
Total Chlorine (ppm): 6 | Free Chlorine (ppm): 6 | Combined Chlorine (ppm): 0 | Total Bromine (ppm): |
Alkalinity (ppm): 120 | Pool water temp ˚F: 80 | pH: | Cyanuric acid (ppm): |
Spa water temp ˚F: | Spa water replaced every 30 days: | Max Allow. Filter Flow (gpm): 141 | Max Allow. Flow: Jet pump capacity (gpm): |
Max Allow. Flow: SF pump capacity (gpm): |
3701-31-04 (B)(4)(a)(iv) / Water temperatures are recorded daily
Repeat Water temperatures were not being recorded daily.
Take and record the water temperature at least once/day.
3701-31-04 (B)(4)(a)(vi) / Total alkalinity is tested weekly
Total alkalinity was not tested weekly.
Test total alkalinity at least once/week.
3701-31-04 (B)(6)(h) / Required meters and gauges maintained/functional
Flow meter was not functioning at time of inspection
Maintain flow meter to funtion at all times while the pool is in operation.
Comments |
---|
-The disinfectant residuals and water quality parameters meet code requirement. -Free chlorine was 6 ppm, ideal range is 2-4 ppm. -All required safety equipment was provided. -The pool perimeter was secure. -The filter pressure was 36 psi. Backwash recommended. -The pool water is clear. If you have any questions or concerns, call me at (513) 732-7602. |