Sampling Details
Sub Type: Other Special Feature: Location:
Area: 1650 Volume (gallons): 51000 Flow measure reading (gpm): 0 Minimum required flow (gpm): 110
Disinfectant: Sodium Hypochlorite Secondary Disinfectant: ORP: 760 Turnover Rate (min): 480
Total Chlorine (ppm): 6 Free Chlorine (ppm): 6 Combined Chlorine (ppm): 0 Total Bromine (ppm):
Alkalinity (ppm): 120 Pool water temp ˚F: 80 pH: Cyanuric acid (ppm):
Spa water temp ˚F: Spa water replaced every 30 days: Max Allow. Filter Flow (gpm): 141 Max Allow. Flow: Jet pump capacity (gpm):
Max Allow. Flow: SF pump capacity (gpm):
[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (B)(4)(a)(iv) / Water temperatures are recorded daily
Repeat Water temperatures were not being recorded daily.
Take and record the water temperature at least once/day.
3701-31-04 (B)(4)(a)(vi) / Total alkalinity is tested weekly
Total alkalinity was not tested weekly.
Test total alkalinity at least once/week.
3701-31-04 (B)(6)(h) / Required meters and gauges maintained/functional
Flow meter was not functioning at time of inspection
Maintain flow meter to funtion at all times while the pool is in operation.


Inspection Information


[?] Facility Type: Pool

[?] Inspection Type: Standard

[?] Inspection Date: 02-August-2017

Comments
-The disinfectant residuals and water quality parameters meet code requirement.
-Free chlorine was 6 ppm, ideal range is 2-4 ppm.
-All required safety equipment was provided.
-The pool perimeter was secure.
-The filter pressure was 36 psi. Backwash recommended.
-The pool water is clear.