Sampling Details | |||
---|---|---|---|
Sub Type: Apartment/Condo | Special Feature: | Location: | |
Area: 1615 | Volume (gallons): 63447 | Flow measure reading (gpm): 100 | Minimum required flow (gpm): 132 |
Disinfectant: Sodium Hypochlorite | Secondary Disinfectant: | ORP: 770 | Turnover Rate (min): 480 |
Total Chlorine (ppm): 3 | Free Chlorine (ppm): 3 | Combined Chlorine (ppm): 0 | Total Bromine (ppm): |
Alkalinity (ppm): 90 | Pool water temp ˚F: 78 | pH: 7.4 | Cyanuric acid (ppm): |
Spa water temp ˚F: | Spa water replaced every 30 days: | Max Allow. Filter Flow (gpm): 98 | Max Allow. Flow: Jet pump capacity (gpm): |
Max Allow. Flow: SF pump capacity (gpm): |
3701-31-04 (B)(6)(h) / Required meters and gauges maintained/functional
Repeat Weirs are missing from the skimmers. Replace the missing weirs.
Maintain all meters and gauges in a properly functioning manner at all times while the pool is in operation. 3701-31-04 (B)(6)(r) / Safety line(s) are maintained
Repeat The safety line was not in place during the inspection. Provide a safety line.
Safety lines must be in place when required to alert the bathers of the change in depth of the pool.
Comments |
---|
Pool Notes: 1. The pool water is clear. 2. ACC unit alarm functioned when tested. Document periodic testing of the ACC unit and the SVRS device. 3. ACC unit pH noted at 7.4. 4. The pool turnover rate=10.6 hours 5. Copy of the report was emailed to Ms. Michelson. Contact Scott Bradley,E.H.S. (732-7614) with any questions. |