Sampling Details
Sub Type: Apartment/Condo Special Feature: Location:
Area: 1615 Volume (gallons): 63447 Flow measure reading (gpm): 100 Minimum required flow (gpm): 132
Disinfectant: Sodium Hypochlorite Secondary Disinfectant: ORP: 770 Turnover Rate (min): 480
Total Chlorine (ppm): 3 Free Chlorine (ppm): 3 Combined Chlorine (ppm): 0 Total Bromine (ppm):
Alkalinity (ppm): 90 Pool water temp ˚F: 78 pH: 7.4 Cyanuric acid (ppm):
Spa water temp ˚F: Spa water replaced every 30 days: Max Allow. Filter Flow (gpm): 98 Max Allow. Flow: Jet pump capacity (gpm):
Max Allow. Flow: SF pump capacity (gpm):
[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (B)(6)(h) / Required meters and gauges maintained/functional
Repeat Weirs are missing from the skimmers. Replace the missing weirs.
Maintain all meters and gauges in a properly functioning manner at all times while the pool is in operation.
3701-31-04 (B)(6)(r) / Safety line(s) are maintained
Repeat The safety line was not in place during the inspection. Provide a safety line.
Safety lines must be in place when required to alert the bathers of the change in depth of the pool.


Inspection Information


[?] Facility Type: Pool

[?] Inspection Type: Standard

[?] Inspection Date: 22-August-2022

Comments
Pool Notes:
1. The pool water is clear.
2. ACC unit alarm functioned when tested. Document periodic testing of the ACC unit and the SVRS device.
3. ACC unit pH noted at 7.4.
4. The pool turnover rate=10.6 hours
5. Copy of the report was emailed to Ms. Michelson.
Contact Scott Bradley,E.H.S. (732-7614) with any questions.