Sampling Details
Sub Type: Apartment/Condo Special Feature: Location:
Area: 880 Volume (gallons): 26400 Flow measure reading (gpm): 95 Minimum required flow (gpm): 40
Disinfectant: Sodium Hypochlorite Secondary Disinfectant: ORP: Turnover Rate (min): 277
Total Chlorine (ppm): 1.25 Free Chlorine (ppm): 1.5 Combined Chlorine (ppm): 0.25 Total Bromine (ppm):
Alkalinity (ppm): 110 Pool water temp ˚F: 87 pH: 7.3 Cyanuric acid (ppm): 30
Spa water temp ˚F: Spa water replaced every 30 days: Max Allow. Filter Flow (gpm): Max Allow. Flow: Jet pump capacity (gpm):
Max Allow. Flow: SF pump capacity (gpm):
[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (A) / All construction or alterations of a public swimming pool are approved
Repeat The installation of the "stingle" switch could not be determined to be approved.
Ensure that the equipment replacement form provided during the last inspection was submitted to the ODH. Once approved, send the appropriate documents to CCPH.


Inspection Information


[?] Facility Type: Pool

[?] Inspection Type: Standard

[?] Inspection Date: 27-June-2016

Comments
1. Pool water was clear.
2. Disinfection residual meet code requirements.
3. The pressure on the filter was noted at 23psi.
4. Pool turnover rate is 4.6 hrs.