Sampling Details | |||
---|---|---|---|
Sub Type: Other | Special Feature: | Location: | |
Area: 1440 | Volume (gallons): 43200 | Flow measure reading (gpm): 0 | Minimum required flow (gpm): 90 |
Disinfectant: Sodium Hypochlorite | Secondary Disinfectant: | ORP: 775 | Turnover Rate (min): |
Total Chlorine (ppm): 3 | Free Chlorine (ppm): 3 | Combined Chlorine (ppm): 0 | Total Bromine (ppm): |
Alkalinity (ppm): 120 | Pool water temp ˚F: 86 | pH: 7.6 | Cyanuric acid (ppm): 0 |
Spa water temp ˚F: | Spa water replaced every 30 days: | Max Allow. Filter Flow (gpm): | Max Allow. Flow: Jet pump capacity (gpm): |
Max Allow. Flow: SF pump capacity (gpm): |
3701-31-04 (B)(2) / Authorized representative is on-site or within 30 minutes of pool location
Authorized representative was not on-site or within 30 minutes of pool location.
Make arrangements to have an authorized representative available while pool is in operation. 3701-31-04 (B)(4)(a)(ii) / Combined chlorine is tested daily at pool side prior to use
Repeat Combined chlorine was not tested daily at pool side prior to use.
Test for combined chlorine prior to bathers entering the water and every 4 hours the pool is open for use. If ACC is in use combined chlorine must be tested every 12 hours while the pool is in use. For spraygrounds and spray features, the combined chlorine must be tested at 1 spray feature every 6 hours the sprayground or spray feature is in use. 3701-31-04 (B)(6)(i) / A means of determining rate-of-flow on all water pumps
A means of determining rate-of-flow was not functioning for water pump.
Properly install a flow meter or have a pump curve available for every water pump used for the pool. 3701-31-04 (B)(6)(s) / Perimeter barrier is in good repair to prevent unauthorized entry
Repeat Main gate is not not self-closing.
Repair gates or doors in order to be self-closing and lockable. Correct By: 16-Jul-2019 3701-31-04 (E)(2)(d) / First aid kit provided
Repeat First aid kit did not contain gloves.
Provide gloves in first aid kit.
Comments |
---|
Pool is hearby ordered closed due to the following safety threat: main gate is not self-closing. Pool is to remain closed and posted as such, until the gate violation is corrected, and verified in writing by this office. Pool water is clear and disinfectant residuals meet minimum code requirements at this time. Pool warning signs are posted as required. Flow meter not functioning during time of inspection. ORP recorded at 775 mv. Reinspection scheduled for 7/16 for gate repair. Pool looks good at this time. |