Sampling Details | |||
---|---|---|---|
Sub Type: Wading Pool | Special Feature: | Location: | |
Area: 100 | Volume (gallons): 780 | Flow measure reading (gpm): 60 | Minimum required flow (gpm): 6.5 |
Disinfectant: Sodium Hypochlorite | Secondary Disinfectant: | ORP: 665 | Turnover Rate (min): 120 |
Total Chlorine (ppm): 8 | Free Chlorine (ppm): 8 | Combined Chlorine (ppm): 0 | Total Bromine (ppm): |
Alkalinity (ppm): 70 | Pool water temp ˚F: 84 | pH: 7.4 | Cyanuric acid (ppm): |
Spa water temp ˚F: | Spa water replaced every 30 days: | Max Allow. Filter Flow (gpm): | Max Allow. Flow: Jet pump capacity (gpm): |
Max Allow. Flow: SF pump capacity (gpm): |
3701-31-04 (B)(4)(a)(vi) / Total alkalinity is tested weekly
Repeat Total alkalinity was not tested weekly.
Test total alkalinity at least once/week. 3701-31-04 (B)(4)(c) / SVRS/APSOS/ACC test results/ service records are maintained
Repeat ACC not tested and recorded monthly.
The test results/service records for these devices must be kept on site for review. If the device has not been recently serviced, have the device tested immediately and provide documentation of the test results. ACC no flow worked at time of inspection. 3701-31-04 (B)(6)(e) / Equipment identification labels are maintained or on file
Repeat Pump model is not on file or on pump.
Replace the missing equipment labels or have the proper equipment information on site for each piece of equipment.
Comments |
---|
- Mulch makes fence at some points only 48" tall. Ensure that further mulch is not added to make fence less than this height. |