Sampling Details
Sub Type: Other Special Feature: Location:
Area: 1160 Volume (gallons): 35500 Flow measure reading (gpm): Minimum required flow (gpm): 74
Disinfectant: Sodium Hypochlorite Secondary Disinfectant: ORP: Turnover Rate (min): 480
Total Chlorine (ppm): 1.5 Free Chlorine (ppm): 1.5 Combined Chlorine (ppm): 0 Total Bromine (ppm):
Alkalinity (ppm): Pool water temp ˚F: 87 pH: 7.5 Cyanuric acid (ppm):
Spa water temp ˚F: Spa water replaced every 30 days: Max Allow. Filter Flow (gpm): 141 Max Allow. Flow: Jet pump capacity (gpm):
Max Allow. Flow: SF pump capacity (gpm):
[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (A)(1) / Public swimming pool is licensed
Repeat The current Swimming Pool License is not posted.
Post the 2018 Swimming Pool License.
3701-31-04 (B) / All facilities are maintained clean, safe and sanitary condition and in good repair.
Repeat No soap is available in the men's rest room.
Provide soap in the men's rest room. Correct By: 27-Aug-2018
3701-31-04 (B)(1)(a) / Outlet covers shall be installed/secured/in compliance
Critical Repeat Specifications for the two (2) main drain covers could not be located.
Provide specifications for the main drain covers to verify VGB compliance.
3701-31-04 (B)(6)(k) / Outlet drain covers are secure/meet ANSI/ASME A112.19.8-2007 requirements.
Critical Repeat Specifications for the two (2) main drain covers could not be located.
Provided specification for the drain covers to verify VGB compliance.


Inspection Information


[?] Facility Type: Pool

[?] Inspection Type: Follow-up

[?] Inspection Date: 27-August-2018

The following violation(s) have been corrected since the last inspection.
3701-31-04 (B)(1)(c)/Minimum disinfection residual shall be maintained as required.
The pool free chorine residual was noted at 0.6ppm.
Increase and maintain the free chlorine residual at 1.0ppm minimum. Correct By: 27-Aug-2018
3701-31-04(D)(6)(a)(2)/Pool free chlorine disinfectant residual shall be above 1 ppm.
Pool free chlorine disinfectant residual was noted at 0.6ppm.
Increase and maintain the free chlorine residual at 1.0ppm minimum. Correct By: 27-Aug-2018
Comments
All other violations were corrected.
Thanks!
1. The pool pH was between 7.4-7.6.
2. The report was emailed to Ms. Butts.
Contact Scott Bradley,R.S. (732-7614) with any questions