Sampling Details
Sub Type: Other Special Feature: Location:
Area: 1800 Volume (gallons): 54000 Flow measure reading (gpm): 120 Minimum required flow (gpm): 113
Disinfectant: Sodium Hypochlorite Secondary Disinfectant: ORP: 607 Turnover Rate (min):
Total Chlorine (ppm): 4 Free Chlorine (ppm): 4 Combined Chlorine (ppm): 0 Total Bromine (ppm):
Alkalinity (ppm): 110 Pool water temp ˚F: 83 pH: 8.0 Cyanuric acid (ppm): 0
Spa water temp ˚F: Spa water replaced every 30 days: Max Allow. Filter Flow (gpm): 74 Max Allow. Flow: Jet pump capacity (gpm):
Max Allow. Flow: SF pump capacity (gpm):
[?] A summary of the violations found during the inspection are listed below.

3701-31-04 ( D )(6)(a) / ORP reading shall be 650 millivolts or greater.
Repeat ORP reading was below 650 mv
Have the ACC unit inspected to determined why the ORP is low.
3701-31-04 (C)(2) / pH is within 7.2 to 7.8
pH was outside the range of 7.2 to 7.8.
Treat the pool water so that the pH is within the acceptable range.


Inspection Information


[?] Facility Type: Pool

[?] Inspection Type: Standard

[?] Inspection Date: 09-August-2019

Comments
Pool water was clear.
Disinfectant residuals meet code requirements at this time.
Observed the "No lifeguard on duty" sign on the ground. Please re-post sign in a location where it is visible.
First aid kits were well supplied.
Emergency phone was functioning during the time of inspection.
Pool looks good, keep up the good work!