Sampling Details
Sub Type: Other Special Feature: Location:
Area: 1840 Volume (gallons): 62400 Flow measure reading (gpm): 107 Minimum required flow (gpm): 130
Disinfectant: Sodium Hypochlorite Secondary Disinfectant: ORP: Turnover Rate (min): 583
Total Chlorine (ppm): 10 Free Chlorine (ppm): 10 Combined Chlorine (ppm): 0 Total Bromine (ppm):
Alkalinity (ppm): Pool water temp ˚F: pH: 8.0 Cyanuric acid (ppm):
Spa water temp ˚F: Spa water replaced every 30 days: Max Allow. Filter Flow (gpm): Max Allow. Flow: Jet pump capacity (gpm):
Max Allow. Flow: SF pump capacity (gpm):
[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (B)(6)(f) / Required turnover rates are sufficient
Repeat Required turnover rates were not met.
Have the circulation system evaluated to determine why the turnover rates are not able to be met. Once the reasons have been determined have the issue repaired. If necessary, submit plans to the Ohio Department of Health to review and approve.


Inspection Information


[?] Facility Type: Pool

[?] Inspection Type: Follow-up

[?] Inspection Date: 23-August-2023

The following violation(s) have been corrected since the last inspection.
3701-31-04 (B)(1)(c)/Minimum disinfection residual shall be maintained as required.
Chlorine disinfectant residual was less than 1 ppm for the pool
Do not operate the pool when the disinfectant residuals are less than what is required. Ensure the chlorine disinfectant residual is at 1 ppm or above prior to placing the pool back into operation.
3701-31-04 (C)(2)/pH is within 7.2 to 7.8
pH was outside the range of 7.2 to 7.8. pH noted to be 8.4
Treat the pool water so that the pH is within the acceptable range.
Comments
Ensure that pH is within range of 7.2-7.8.