Sampling Details | |||
---|---|---|---|
Sub Type: Other | Special Feature: | Location: | |
Area: 1325 | Volume (gallons): 39750 | Flow measure reading (gpm): 0 | Minimum required flow (gpm): 83 |
Disinfectant: Sodium Hypochlorite | Secondary Disinfectant: | ORP: 720 | Turnover Rate (min): 480 |
Total Chlorine (ppm): 3 | Free Chlorine (ppm): 3 | Combined Chlorine (ppm): 0 | Total Bromine (ppm): |
Alkalinity (ppm): 100 | Pool water temp ˚F: 84 | pH: 7.4 | Cyanuric acid (ppm): 16 |
Spa water temp ˚F: | Spa water replaced every 30 days: | Max Allow. Filter Flow (gpm): 141 | Max Allow. Flow: Jet pump capacity (gpm): |
Max Allow. Flow: SF pump capacity (gpm): |
3701-31-04 (B)(4)(a)(ii) / Combined chlorine is tested daily at pool side prior to use
Combined chlorine was not tested every 12 hours.
If ACC is in use combined chlorine must be tested every 12 hours while the pool is in use.
3701-31-04 (B)(4)(a)(iii) / pH is tested daily at pool side at required intervals for pools/automatic chemical controllers/special features
pH was not tested daily at pool side and/or at required intervals for pools/automatic chemical controllers/special features.
If ACC is in use pH must be tested every 12 hours while the pool is in use.
3701-31-04 (B)(4)(a)(iv) / Water temperatures are recorded daily
Repeat Water temperatures were not being recorded daily.
Take and record the water temperature at least once/day.
3701-31-04 (B)(6)(h) / Required meters and gauges maintained/functional
Flow meter was not functioning properly.
Repair flow meter to function properly.
3701-31-04 (B)(6)(o) / Ladders/stairs/steps are in good repair/slip resistent
Repeat Ladder on the side closest to the far stairs was loose and lifing from the ground.
Repair or replace the ladder so that they are slip resistant and in good repair.
3701-31-04 (E)(2)(d) / First aid kit provided
Repeat First aid kit did not have disposable gloves.
Provide disposable gloves in kit, at the pool at all times.
Comments |
---|
-Ensure the following for record requirements: -The pool is open for 13 hours Sunday-Thursday and then for 15 hours on Friday - Saturday. Code states that pools using an ACC must test and record free chlorine, combined chlorine, and pH every 12 hours. -Shorten pool hours or test/record every 12 hours. -The disinfectant residuals and water quality parameters meet code requirement. -All required safety equipment was provided. -The pool perimeter was secure. -The filter pressure was 24 psi. -The pool water was clear. -The ACC unit measured pH at 7.5 -Recommend that the head restraint and straps on spine board are removed since there is no lifeguard on duty. If you have any questions or concerns, call Mackinzie Dickman at (513) 732-7602. |