Sampling Details | |||
---|---|---|---|
Sub Type: Apartment/Condo | Special Feature: | Location: | |
Area: 880 | Volume (gallons): 26400 | Flow measure reading (gpm): 70 | Minimum required flow (gpm): 63 |
Disinfectant: Sodium Hypochlorite | Secondary Disinfectant: | ORP: | Turnover Rate (min): 480 |
Total Chlorine (ppm): 1.5 | Free Chlorine (ppm): 1.5 | Combined Chlorine (ppm): 0 | Total Bromine (ppm): |
Alkalinity (ppm): 80 | Pool water temp ˚F: 79 | pH: 7.4 | Cyanuric acid (ppm): |
Spa water temp ˚F: | Spa water replaced every 30 days: | Max Allow. Filter Flow (gpm): | Max Allow. Flow: Jet pump capacity (gpm): |
Max Allow. Flow: SF pump capacity (gpm): |
3701-31-04 (A) / All construction or alterations of a public swimming pool are approved
The installation of the "Stingl" switch could not be determined to be approved.
Continue efforts to obtain approval from the Ohio Department of Health. 3701-31-04 (B)(6) / Equipment is maintained per manufacturers specifications.
The five (5) foot skimmer basket weir is missing.
Replace the missing weir. 3701-31-04 (B)(6)(k) / Outlet drain covers are secure/meet ANSI/ASME A112.19.8-2007 requirements.
Critical Repeat Specifications for the drain cover has not been provided.
Provide specifications for the drain cover to verify VGB compliance.
Comments |
---|
Pool Notes: 1. Pressure gauge noted at 10psi. 2. Turnover rate=6.3 hours. Inspection conducted by Scott Bradley,R.S. 732-7614 |