Sampling Details
Sub Type: Apartment/Condo Special Feature: Location:
Area: 880 Volume (gallons): 26400 Flow measure reading (gpm): 70 Minimum required flow (gpm): 63
Disinfectant: Sodium Hypochlorite Secondary Disinfectant: ORP: Turnover Rate (min): 480
Total Chlorine (ppm): 1.5 Free Chlorine (ppm): 1.5 Combined Chlorine (ppm): 0 Total Bromine (ppm):
Alkalinity (ppm): 80 Pool water temp ˚F: 79 pH: 7.4 Cyanuric acid (ppm):
Spa water temp ˚F: Spa water replaced every 30 days: Max Allow. Filter Flow (gpm): Max Allow. Flow: Jet pump capacity (gpm):
Max Allow. Flow: SF pump capacity (gpm):
[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (A) / All construction or alterations of a public swimming pool are approved
The installation of the "Stingl" switch could not be determined to be approved.
Continue efforts to obtain approval from the Ohio Department of Health.
3701-31-04 (B)(6) / Equipment is maintained per manufacturers specifications.
The five (5) foot skimmer basket weir is missing.
Replace the missing weir.
3701-31-04 (B)(6)(k) / Outlet drain covers are secure/meet ANSI/ASME A112.19.8-2007 requirements.
Critical Repeat Specifications for the drain cover has not been provided.
Provide specifications for the drain cover to verify VGB compliance.


Inspection Information


[?] Facility Type: Pool

[?] Inspection Type: Standard

[?] Inspection Date: 14-August-2014

Comments
Pool Notes:
1. Pressure gauge noted at 10psi.
2. Turnover rate=6.3 hours.
Inspection conducted by Scott Bradley,R.S. 732-7614