Sampling Details
Sub Type: Other Special Feature: Location:
Area: 1800 Volume (gallons): 54000 Flow measure reading (gpm): 100 Minimum required flow (gpm): 113
Disinfectant: Sodium Hypochlorite Secondary Disinfectant: ORP: Turnover Rate (min): 480
Total Chlorine (ppm): 2 Free Chlorine (ppm): 2 Combined Chlorine (ppm): 0 Total Bromine (ppm):
Alkalinity (ppm): 100 Pool water temp ˚F: 85 pH: 7.4 Cyanuric acid (ppm):
Spa water temp ˚F: Spa water replaced every 30 days: Max Allow. Filter Flow (gpm): Max Allow. Flow: Jet pump capacity (gpm):
Max Allow. Flow: SF pump capacity (gpm):
[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (B)(1)(a) / Outlet covers shall be installed/secured/in compliance
Critical Repeat The main drain cover has passed the required replacement date.
Replace the cover to verify VGB compliance.
3701-31-04 (B)(4)(a)(vi) / Total alkalinity is tested weekly
Repeat Total alkalinity was not tested weekly.
Test and record the pool total alkalinity at least once each week. Correct By: 16-Aug-2018
3701-31-04 (B)(6)(h) / Required meters and gauges maintained/functional
Repeat Weirs are missing in the skimmer baskets
Replace the missing weirs.
3701-31-04 (B)(6)(k) / Outlet drain covers are secure/meet ANSI/ASME A112.19.8-2007 requirements.
Critical Repeat The main drain cover has passed the required replacement date.
Replace the cover to verify VGB compliance.
3701-31-04 (E)(2)(d) / First aid kit provided
Gloves were not provided in the first aid kit.
Provide gloves for the first aid kit. Correct By: 16-Aug-2018


Inspection Information


[?] Facility Type: Pool

[?] Inspection Type: Standard

[?] Inspection Date: 10-August-2018

Comments
No other violations observed during the inspection.
Pool Notes:
1. The pool water is clear.
2. Pool turnover rate was noted at 9 hours. For an eight (8) hour turnover, a flow rate of 113gpm is recommended.
3. The pool pH was between 7.6-7.8.
4. One (1) lifeguard was on duty during the inspection.
5. The 2018 pool license is posted.
6. The report was emailed to Mr. Hooker
Contact Scott Bradley,R.S. (732-7614) with any questions.