Sampling Details | |||
---|---|---|---|
Sub Type: Other | Special Feature: | Location: | |
Area: 1800 | Volume (gallons): 54000 | Flow measure reading (gpm): 90 | Minimum required flow (gpm): 113 |
Disinfectant: Sodium Hypochlorite | Secondary Disinfectant: | ORP: | Turnover Rate (min): 480 |
Total Chlorine (ppm): 0 | Free Chlorine (ppm): 0 | Combined Chlorine (ppm): 0 | Total Bromine (ppm): |
Alkalinity (ppm): 100 | Pool water temp ˚F: 83 | pH: 7.6 | Cyanuric acid (ppm): |
Spa water temp ˚F: | Spa water replaced every 30 days: | Max Allow. Filter Flow (gpm): | Max Allow. Flow: Jet pump capacity (gpm): |
Max Allow. Flow: SF pump capacity (gpm): |
3701-31-04 (B)(1)(c) / Minimum disinfection residual shall be maintained as required.
Critical The pool free chlorine residual was noted at 0ppm.
Increase and maintain the pool free chlorine level at 1.0ppm. According to the life guard (Peter) the feeder may have been turned off at the end of the day on 8/28/17.
Peter agreed to Voluntarily Close the pool. Correct By: 30-Aug-2017
3701-31-04 (B)(4)(a)(vi) / Total alkalinity is tested weekly
Repeat Total alkalinity was not tested weekly.
Test and record the pool alkalinity at least once weekly.
3701-31-04 (B)(6) / Equipment is maintained per manufacturers specifications.
Repeat Weirs are missing in the three (3) and five (5) foot end skimmer baskets.
Replace the missing weirs.
3701-31-04(D)(6)(a)(2) / Pool free chlorine disinfectant residual shall be above 1 ppm.
Critical Repeat The pool free chlorine residual was noted at 0 ppm.
Increase and maintain the pool free chlorine level at 1.0ppm. According to the life guard (Peter) the feeder may have been turned off at the end of the day on 8/28/17.
Peter agreed to Voluntarily Close the pool. Correct By: 30-Aug-2017
Comments |
---|
Wading Pool Notes: 1. The pool water is clear. 2. Wading pool turnover rate noted at 10 hours. For an eight (8) hour turnover, a flow rate of 113gpm is recommended. 3. Pressure gauge noted at 25psi. 4. One (1) lifeguard was on duty during the inspection. 5. The 2017 pool license is posted. 6. The report was emailed to Mr. Henke Contact Scott Bradley,R.S. (732-7614) with any questions. |