Sampling Details
Sub Type: School Special Feature: Location:
Area: 1800 Volume (gallons): 65000 Flow measure reading (gpm): 0 Minimum required flow (gpm): 168
Disinfectant: Sodium Hypochlorite Secondary Disinfectant: ORP: 790 Turnover Rate (min):
Total Chlorine (ppm): 3 Free Chlorine (ppm): 3 Combined Chlorine (ppm): 0 Total Bromine (ppm):
Alkalinity (ppm): 30 Pool water temp ˚F: 80 pH: 7.6 Cyanuric acid (ppm):
Spa water temp ˚F: Spa water replaced every 30 days: Max Allow. Filter Flow (gpm): 282 Max Allow. Flow: Jet pump capacity (gpm):
Max Allow. Flow: SF pump capacity (gpm):
[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (B)(6)(i) / A means of determining rate-of-flow on all water pumps
Repeat A means of determining rate-of-flow was not functioning for water pump.
Properly install a flow meter or have a pump curve available for every water pump used for the pool.
3701-31-04 (C)(3) / Total alkalinity is at or greater than 60 ppm
Repeat Total alkalinity was less than 60 ppm.
Raise the total alkalinity to at least 60 ppm.


Inspection Information


[?] Facility Type: Pool

[?] Inspection Type: Standard

[?] Inspection Date: 02-August-2019

Comments
Pool water was clear.
Disinfectant residuals meet minimum code requirements at this time.
Alkalinity was observed low (<60ppm) during inspection.
Flow meter was not functioning during inspection.
Safety equipment and signs provided.
ACC unit tested during inspection, visual no flow alarm observed.
Pool looks good. Keep up the good work!