Sampling Details | |||
---|---|---|---|
Sub Type: Other | Special Feature: | Location: | |
Area: 1840 | Volume (gallons): 62400 | Flow measure reading (gpm): 100 | Minimum required flow (gpm): 130 |
Disinfectant: Sodium Hypochlorite | Secondary Disinfectant: | ORP: 701 | Turnover Rate (min): 480 |
Total Chlorine (ppm): 8 | Free Chlorine (ppm): 8 | Combined Chlorine (ppm): 0 | Total Bromine (ppm): |
Alkalinity (ppm): 90 | Pool water temp ˚F: 82 | pH: 7.2 | Cyanuric acid (ppm): |
Spa water temp ˚F: | Spa water replaced every 30 days: | Max Allow. Filter Flow (gpm): 141 | Max Allow. Flow: Jet pump capacity (gpm): |
Max Allow. Flow: SF pump capacity (gpm): |
3701-31-04 (B)(1)(e) / Automatic Chemical Controller (ACC) shall function properly.
Critical Repeat Corrected During Inspection Automatic Chemical Controller (ACC) was not functioning properly at the time of the inspection
Do not operate the pool when the ACC unit is not functioning properly. Ensure that the ACC unit is functioning properly prior to placing the pool back into operation. 3701-31-04 (B)(6)(c) / Cross connection hazards shall be prevented.
Corrected During Inspection Hose for filling acid tank in pump room did not have backflow device on.
Hose was disconnected from hose bibb. If hose is re-attached, an appropriate backflow prevention device must be provided. 3701-31-04 (B)(6)(i) / A means of determining rate-of-flow on all water pumps
Flow meter is at top of capacity and only goes from 18-90 gpm.
Properly install a flow meter or have a pump curve available for every water pump used for the pool.
Comments |
---|
Less than 30 ppm cyanuric Acid Pool Water was clear. Safety Equipment provided |