Sampling Details
Sub Type: Apartment/Condo Special Feature: Location:
Area: 985 Volume (gallons): 29500 Flow measure reading (gpm): 110 Minimum required flow (gpm): 61
Disinfectant: Sodium Hypochlorite Secondary Disinfectant: ORP: 720 Turnover Rate (min): 480
Total Chlorine (ppm): 4 Free Chlorine (ppm): 4 Combined Chlorine (ppm): 0 Total Bromine (ppm):
Alkalinity (ppm): 110 Pool water temp ˚F: 82 pH: 7.6 Cyanuric acid (ppm):
Spa water temp ˚F: Spa water replaced every 30 days: Max Allow. Filter Flow (gpm): 98 Max Allow. Flow: Jet pump capacity (gpm):
Max Allow. Flow: SF pump capacity (gpm):
[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (B)(1)(a) / Outlet covers shall be installed/secured/in compliance
Critical The main drain cover replaced in July 2005 had a five (5) year life span.
Replace the cover to verify VGB compliance.
3701-31-04 (B)(6)(k) / Outlet drain covers are secure/meet ANSI/ASME A112.19.8-2007 requirements.
Critical Repeat The main drain cover replaced in July 2005 had a five (5) year life span.
Replace the main drain cover to verify VGB compliance.


Inspection Information


[?] Facility Type: Pool

[?] Inspection Type: Standard

[?] Inspection Date: 01-August-2017

Comments
No other violation observed during the inspection.
The pool otherwise Looks Great!
Pool Notes:
1. The pool water is clear.
2. ACC unit pH noted at 7.7.
3. ACC alarm functions when tested.
4. ACC and SVRS device testing is documented in the pool records.
5. Pool turnover rate=4.5 hours.
6. The report was emailed to Mr. Sinkovich.
Contact Scott Bradley,R.S. (732-7614) with any questions.