Sampling Details | |||
---|---|---|---|
Sub Type: Other | Special Feature: | Location: | |
Area: 1650 | Volume (gallons): 51000 | Flow measure reading (gpm): 120 | Minimum required flow (gpm): 110 |
Disinfectant: Sodium Hypochlorite | Secondary Disinfectant: | ORP: 708 | Turnover Rate (min): 480 |
Total Chlorine (ppm): 8 | Free Chlorine (ppm): 8 | Combined Chlorine (ppm): 0 | Total Bromine (ppm): |
Alkalinity (ppm): 100 | Pool water temp ˚F: 80 | pH: 7.5 | Cyanuric acid (ppm): |
Spa water temp ˚F: | Spa water replaced every 30 days: | Max Allow. Filter Flow (gpm): 141 | Max Allow. Flow: Jet pump capacity (gpm): |
Max Allow. Flow: SF pump capacity (gpm): |
3701-31-04 (E)(2)(d) / First aid kit provided
Gloves were not supplied in the first aid kit.
Supply gloves in the first aid kit. 3701-31-04 (E)(3)(a) / "WARNING, NO LIFEGUARD", sign posted
Repeat The unguarded pool was in use without the "WARNING, NO LIFEGUARD" sign posted.
Post the WARNING, NO LIFEGUARD sign in a conspicuos location at all times the pool is available for use.
Comments |
---|
1. The disinfectant residuals and water quality parameters meet code requirements. 2. All required safety equipment was provided (except gloves). 3. The pool perimeter was secure. 4. The pool water was clear. 5. The ACC measured pH at 7.7. Consider calibrating ACC pH probe. 6. Turnover rate was 7.1 hours. If you have any questions or concerns, call me at (513) 732-7612. |