Sampling Details | |||
---|---|---|---|
Sub Type: Other | Special Feature: | Location: | |
Area: 1696 | Volume (gallons): 52000 | Flow measure reading (gpm): 100 | Minimum required flow (gpm): 109 |
Disinfectant: Sodium Hypochlorite | Secondary Disinfectant: | ORP: 711 | Turnover Rate (min): 480 |
Total Chlorine (ppm): 2.5 | Free Chlorine (ppm): 2.5 | Combined Chlorine (ppm): 0 | Total Bromine (ppm): |
Alkalinity (ppm): 140 | Pool water temp ˚F: 78 | pH: 7.4 | Cyanuric acid (ppm): |
Spa water temp ˚F: | Spa water replaced every 30 days: | Max Allow. Filter Flow (gpm): 74 | Max Allow. Flow: Jet pump capacity (gpm): |
Max Allow. Flow: SF pump capacity (gpm): |
3701-31-04 (D)(7)(c) / Audible/visual alarm shall activate when unit is malfunctioning or when pH or ORP levels are not acceptable.
Critical The ACC unit alarm could not be tested.
Determine a way to test the ACC unit alarm to insure it will function when activated. Correct By: 30-Jun-2015
Comments |
---|
No other violations observed during the inspection. The pool otherwise looks great! Pool Notes: 1. The 2015 pool license is posted. 2. The pool water is clear. 3. Proper safety equipment is available for use. 4. ACC unit pH noted at 7.8. 5. Pool turnover rate=8.7 hours. A flow rate of 108-110gpm would need to be maintained to insure an eight (8) hour turnover rate. 6. Copy of the report was left with the pool records. Inspection conducted by Scott Bradley,R.S. 732-7614 |