Sampling Details
Sub Type: Wading Pool Special Feature: Location:
Area: 225 Volume (gallons): 2531 Flow measure reading (gpm): 65 Minimum required flow (gpm): 6
Disinfectant: Sodium Hypochlorite Secondary Disinfectant: ORP: 730 Turnover Rate (min): 38
Total Chlorine (ppm): 2.5 Free Chlorine (ppm): 2.5 Combined Chlorine (ppm): 0 Total Bromine (ppm):
Alkalinity (ppm): 40 Pool water temp ˚F: 80 pH: 8.0 Cyanuric acid (ppm):
Spa water temp ˚F: Spa water replaced every 30 days: Max Allow. Filter Flow (gpm): Max Allow. Flow: Jet pump capacity (gpm):
Max Allow. Flow: SF pump capacity (gpm):
[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (B)(4)(a)(iv) / Water temperatures are recorded daily
Repeat Water temperatures were not being recorded daily.
Take and record the water temperature at least once/day.
3701-31-04 (B)(4)(a)(vi) / Total alkalinity is tested weekly
Repeat Total alkalinity was not tested weekly.
Test total alkalinity at least once/week.
3701-31-04 (B)(6)(h) / Required meters and gauges maintained/functional
Flow sensor was not properly hooked up.
Ensure flow sensor is hooked up to ACC,


Inspection Information


[?] Facility Type: Pool

[?] Inspection Type: Standard

[?] Inspection Date: 15-July-2024

Comments
Notes:
-Pool water was noted low.
-Recommended to put club house address by phone.
-First aid kit was missing at time of inspection. Pool operator arrived and stated they had an extra.
-Flow sensors were not properly plugged in. Follow up to confirm sensors are properly plugged in and 'No Flow' alarm is working.