Sampling Details | |||
---|---|---|---|
Sub Type: Wading Pool | Special Feature: | Location: | |
Area: 225 | Volume (gallons): 2531 | Flow measure reading (gpm): 65 | Minimum required flow (gpm): 6 |
Disinfectant: Sodium Hypochlorite | Secondary Disinfectant: | ORP: 730 | Turnover Rate (min): 38 |
Total Chlorine (ppm): 2.5 | Free Chlorine (ppm): 2.5 | Combined Chlorine (ppm): 0 | Total Bromine (ppm): |
Alkalinity (ppm): 40 | Pool water temp ˚F: 80 | pH: 8.0 | Cyanuric acid (ppm): |
Spa water temp ˚F: | Spa water replaced every 30 days: | Max Allow. Filter Flow (gpm): | Max Allow. Flow: Jet pump capacity (gpm): |
Max Allow. Flow: SF pump capacity (gpm): |
3701-31-04 (B)(4)(a)(iv) / Water temperatures are recorded daily
Repeat Water temperatures were not being recorded daily.
Take and record the water temperature at least once/day. 3701-31-04 (B)(4)(a)(vi) / Total alkalinity is tested weekly
Repeat Total alkalinity was not tested weekly.
Test total alkalinity at least once/week. 3701-31-04 (B)(6)(h) / Required meters and gauges maintained/functional
Flow sensor was not properly hooked up.
Ensure flow sensor is hooked up to ACC,
Comments |
---|
Notes: -Pool water was noted low. -Recommended to put club house address by phone. -First aid kit was missing at time of inspection. Pool operator arrived and stated they had an extra. -Flow sensors were not properly plugged in. Follow up to confirm sensors are properly plugged in and 'No Flow' alarm is working. |