Sampling Details | |||
---|---|---|---|
Sub Type: Hotel/motel | Special Feature: | Location: | |
Area: 490 | Volume (gallons): 12795 | Flow measure reading (gpm): 50 | Minimum required flow (gpm): 27 |
Disinfectant: Salt | Secondary Disinfectant: | ORP: 511 | Turnover Rate (min): 255 |
Total Chlorine (ppm): 1.25 | Free Chlorine (ppm): 1.25 | Combined Chlorine (ppm): 0 | Total Bromine (ppm): 0 |
Alkalinity (ppm): 70 | Pool water temp ˚F: 80 | pH: 7.4 | Cyanuric acid (ppm): 0 |
Spa water temp ˚F: | Spa water replaced every 30 days: | Max Allow. Filter Flow (gpm): | Max Allow. Flow: Jet pump capacity (gpm): |
Max Allow. Flow: SF pump capacity (gpm): |
3701-31-04 ( D )(6)(a) / ORP reading shall be 650 millivolts or greater.
ORP reading was below 650 mv. Observed at 511 mv.
Have the ACC unit inspected to determined why the ORP is low.
Comments |
---|
-The disinfectant residuals and water quality parameters meet code requirement. The free chlorine was observed at 1.25 ppm, this is above the minimum requirement of 1.0 ppm for pools. However, the recommended range is 2-4 ppm. Make sure the free chlorine stays above 1.0 ppm. -pH was measured at 7.4. -All required safety equipment was provided. -The pool perimeter was secure. -The filter pressure was 10 psi on both filters. -Turn over rate was 306 minutes. - The facility uses salt and acid to create chlorine. Therefore the pool is disinfected using chlorine. If you have any questions or concerns, call Bela Perler at 513-732-7612. |