Sampling Details | |||
---|---|---|---|
Sub Type: Other | Special Feature: | Location: | |
Area: 1650 | Volume (gallons): 51000 | Flow measure reading (gpm): 120 | Minimum required flow (gpm): 110 |
Disinfectant: Sodium Hypochlorite | Secondary Disinfectant: | ORP: 770 | Turnover Rate (min): 480 |
Total Chlorine (ppm): 8 | Free Chlorine (ppm): 8 | Combined Chlorine (ppm): 0 | Total Bromine (ppm): |
Alkalinity (ppm): 90 | Pool water temp ˚F: 85 | pH: 7.5 | Cyanuric acid (ppm): 0 |
Spa water temp ˚F: | Spa water replaced every 30 days: | Max Allow. Filter Flow (gpm): 141 | Max Allow. Flow: Jet pump capacity (gpm): |
Max Allow. Flow: SF pump capacity (gpm): |
3701-31-04 (B)(4)(a)(iv) / Water temperatures are recorded daily
Water temperatures were not being recorded daily.
Take and record the water temperature at least once/day. 3701-31-04 (B)(4)(a)(ix) / Chemicals added to the pool other than those used for disinfection
Chemicals added to the pool other than those used for disinfection were not being recorded.
Facility records must indicate when chemicals, other than disinfectants, are added to the pool water. 3701-31-04 (B)(6) / Equipment is maintained per manufacturers specifications.
Repeat Two skimmer weirs were missing.
Replace the missing skimmer weirs. 3701-31-04 (D)(7)(d) / Flow or pressure switch with a shut off valve shall be provided and tested monthly.
Critical Corrected During Inspection Flow switch for ACC shut off valve was not tested and recorded monthly.
Provide records indicating that the unit is being tested monthly. The flow switch functioned properly.
Comments |
---|
-The disinfectant residuals and water quality parameters meet code requirement. -Free chlorine was 8 ppm, ideal range is 2-4 ppm. -All required safety equipment was provided. -The pool perimeter was secure. -The filter pressure was 12 psi. -The pool water is clear. -The ACC unit measured pH at 7.4. -Turn over rate was 425 minutes. If you have any questions or concerns, call me at (513) 732-7612. |