Sampling Details | |||
---|---|---|---|
Sub Type: Wading Pool | Special Feature: | Location: | |
Area: 136 | Volume (gallons): 1530 | Flow measure reading (gpm): | Minimum required flow (gpm): |
Disinfectant: Sodium Hypochlorite | Secondary Disinfectant: | ORP: | Turnover Rate (min): 120 |
Total Chlorine (ppm): 1.5 | Free Chlorine (ppm): 1.5 | Combined Chlorine (ppm): 0 | Total Bromine (ppm): |
Alkalinity (ppm): | Pool water temp ˚F: | pH: 7.4 | Cyanuric acid (ppm): |
Spa water temp ˚F: | Spa water replaced every 30 days: | Max Allow. Filter Flow (gpm): | Max Allow. Flow: Jet pump capacity (gpm): |
Max Allow. Flow: SF pump capacity (gpm): |
No critical violations were documented at the time of inspection.
No violations were documented at the time of inspection.
The following violation(s) have been corrected since the last inspection. |
---|
3701-31-04 (C)(2)/pH is within 7.2 to 7.8 The baby pool pH was noted at 6.8. Seven (7) drops of base demand reagent raised the pH to 7.2. Raise and maintain the pH of the baby pool between 7.2-7.8. Correct By: 08-Jul-2014 Ms. Michelson agreed to voluntarily close the pool. pH adjustment chemicals were added. Correct By: 17-Jul-2014 |
3701-31-04 (D)(6)(a)/Pool free chlorine disinfectant residual is above 1 ppm. Pool free chlorine disinfectant residual was noted at 0.6ppm. Raise and maintain the free chlorine level at 1ppm minimum. Correct By: 17-Jul-2014 |
3701-31-04 (D)(7)(c)/Audible/visual alarm when unit is malfunctioning or when pH or ORP levels are not acceptable. The ACC unit auto shut off function could not be determined. Determine a way to test the ACC unit automatic shut off. Correct By: 17-Jul-2014 |
3701-31-04 (B)(6)/Equipment is maintained per manufacturers specifications. The skimmer weir is missing. Replace the missing skimmer weir. Correct By: 17-Jul-2014 |
Comments |
---|
All violations corrected. Thanks! Note: The 7/17/2014 reinspection was rescheduled. Reinspection conducted by Scott Bradley,R.S. 732-7614 |