Sampling Details
Sub Type: School Special Feature: Location:
Area: 1800 Volume (gallons): 65000 Flow measure reading (gpm): 0 Minimum required flow (gpm): 135
Disinfectant: Calcium Hypochlorite Secondary Disinfectant: ORP: 650 Turnover Rate (min): 480
Total Chlorine (ppm): 5 Free Chlorine (ppm): 5 Combined Chlorine (ppm): 0 Total Bromine (ppm):
Alkalinity (ppm): 70 Pool water temp ˚F: 89 pH: 7.2 Cyanuric acid (ppm): 0
Spa water temp ˚F: Spa water replaced every 30 days: Max Allow. Filter Flow (gpm): Max Allow. Flow: Jet pump capacity (gpm):
Max Allow. Flow: SF pump capacity (gpm):
[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (B)(4)(a)(ii) / Combined chlorine is tested daily at pool side prior to use
Combined chlorine was not tested daily at pool side prior to use. Readings are being recorded daily without the use of reagent #3 (the bottle is still completely full).
Test for combined chlorine (by adding 5 drops of reagent #3 to the free chlorine sample and record )prior to bathers entering the water and every 12 hours while the pool is in use.
3701-31-04 (B)(6)(h) / Required meters and gauges maintained/functional
Float(s) appear to be stuck in the flow meter(s).
Repair flow meters so that flow rate can be monitored and assured. Maintain all meters and gauges in a properly funtioning manner at all times while the pool is in operation.


Inspection Information


[?] Facility Type: Pool

[?] Inspection Type: Standard

[?] Inspection Date: 29-February-2016

Comments
Notes:
Disinfectant residual & water quality reading meet minimum code requirements at this time. Thank you.
Water clarity is superb at this time.
Pool is well maintained at this time.
Safety equipment & signage provided as required.

After a one year hiatus, Clermont County Public Health will once again be hosting a 3-hour public swimming pool compliance training class free of charge on April 26, 2016 in the Large Conference Room at Permit Central, 2275 Bauer Rd., Batavia, OH 45103.