Sampling Details
Sub Type: Other Special Feature: Location:
Area: 1000 Volume (gallons): 30000 Flow measure reading (gpm): 50 Minimum required flow (gpm): 60
Disinfectant: Sodium Hypochlorite Secondary Disinfectant: ORP: 686 Turnover Rate (min): 480
Total Chlorine (ppm): 7 Free Chlorine (ppm): 7 Combined Chlorine (ppm): 0 Total Bromine (ppm):
Alkalinity (ppm): 130 Pool water temp ˚F: 81 pH: 7.7 Cyanuric acid (ppm): 20
Spa water temp ˚F: Spa water replaced every 30 days: Max Allow. Filter Flow (gpm): 74 Max Allow. Flow: Jet pump capacity (gpm):
Max Allow. Flow: SF pump capacity (gpm):
[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (B)(4) / The licensee /authorized representative is keeping records
The licensee /authorized representative was not keeping all required operational records.
All required tests at code specified frequencies must be recorded in the daily pool operation reports.
3701-31-04 (B)(6)(f) / Required turnover rates are sufficient
Repeat Required turnover rates were not met. Observed flow rate is 10 gpm less than necessary to achieve 8 hour turnover rate.
If possible, throttle the flow to at least 60 gpm so as to achieve 8 hour turnover rate as required, If necessary, have the circulation system evaluated to determine why the turnover rates are not able to be met. Once the reasons have been determined have the issue repaired. If required, submit plans to the Ohio Department of Health to review and approve.


Inspection Information


[?] Facility Type: Pool

[?] Inspection Type: Standard

[?] Inspection Date: 17-August-2015

Comments
Pool inspection notes:
Water clarity, disinfectant residuals (though higher than necessary at 7 ppm), and water quality readings meet minimum code requirements at this time.
Signage and safety equipment provided as required.
Pool looks really good. Thanks for a good pool season.