Sampling Details
Sub Type: Apartment/Condo Special Feature: Location:
Area: 985 Volume (gallons): 29500 Flow measure reading (gpm): 120 Minimum required flow (gpm): 61
Disinfectant: Sodium Hypochlorite Secondary Disinfectant: ORP: 700 Turnover Rate (min): 480
Total Chlorine (ppm): 4 Free Chlorine (ppm): 4 Combined Chlorine (ppm): 0 Total Bromine (ppm):
Alkalinity (ppm): 170 Pool water temp ˚F: 84 pH: 7.6 Cyanuric acid (ppm):
Spa water temp ˚F: Spa water replaced every 30 days: Max Allow. Filter Flow (gpm): 98 Max Allow. Flow: Jet pump capacity (gpm):
Max Allow. Flow: SF pump capacity (gpm):
[?] A summary of the violations found during the inspection are listed below.

No critical violations were documented at the time of inspection.

No violations were documented at the time of inspection.


Inspection Information


[?] Facility Type: Pool

[?] Inspection Type: Standard

[?] Inspection Date: 01-August-2019

Comments
No violations observed during the inspection.
The pool otherwise Looks Great!
Pool Notes:
1. The pool water is clear.
2. ACC unit pH noted at 7.6.
3. ACC alarm functions when tested.
4. All required safety equipment is available.
5. ACC and SVRS device testing is documented in the pool records
6. Filter pressure gauge noted at 10psi.
7. Pool turnover rate=4.1hours.
8. According to information posted at the facility, the pool main drain cover was replaced in April 2018.
9. The report was emailed to Mr. Sinkovich.
Contact Scott Bradley,R.S. (732-7614) with any questions.