Sampling Details
Sub Type: Other Special Feature: Location:
Area: 1325 Volume (gallons): 39750 Flow measure reading (gpm): 80 Minimum required flow (gpm): 83
Disinfectant: Sodium Hypochlorite Secondary Disinfectant: ORP: 770 Turnover Rate (min): 480
Total Chlorine (ppm): 2.5 Free Chlorine (ppm): 2.5 Combined Chlorine (ppm): 0 Total Bromine (ppm):
Alkalinity (ppm): 150 Pool water temp ˚F: 82 pH: 7.6 Cyanuric acid (ppm):
Spa water temp ˚F: Spa water replaced every 30 days: Max Allow. Filter Flow (gpm): 141 Max Allow. Flow: Jet pump capacity (gpm):
Max Allow. Flow: SF pump capacity (gpm):
[?] A summary of the violations found during the inspection are listed below.

No critical violations were documented at the time of inspection.

No violations were documented at the time of inspection.


Inspection Information


[?] Facility Type: Pool

[?] Inspection Type: Standard

[?] Inspection Date: 21-June-2022

Comments
--No violations observed at time of inspection.
--Per information on file, pool main drain covers were due to be replaced in 2021. Replace main drain cover and submit certificates of compliance, make/model information along with expiration dates. In the alternative, submit updated information on drain covers indicated that they have been replaced.
--Appears that the paver stones at the south east corner of the pool are sinking creating a gap between the bottom of the perimeter fencing and ground. At no time shall a gap within the perimeter barrier and a building, or the ground exceed four inches. Ensure gap between bottom of perimeter barrier and ground does not exceed four inches at any location.