Sampling Details
Sub Type: Other Special Feature: Location:
Area: 1000 Volume (gallons): 30000 Flow measure reading (gpm): 0 Minimum required flow (gpm): 63
Disinfectant: Sodium Hypochlorite Secondary Disinfectant: ORP: 676 Turnover Rate (min): 480
Total Chlorine (ppm): 2 Free Chlorine (ppm): 2 Combined Chlorine (ppm): 0 Total Bromine (ppm):
Alkalinity (ppm): 110 Pool water temp ˚F: 82 pH: 7.5 Cyanuric acid (ppm): 0
Spa water temp ˚F: Spa water replaced every 30 days: Max Allow. Filter Flow (gpm): 75 Max Allow. Flow: Jet pump capacity (gpm):
Max Allow. Flow: SF pump capacity (gpm):
[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (B)(6)(i) / A means of determining rate-of-flow on all water pumps
A means of determining rate-of-flow was not found for the circulation pump. Flow meter has been removed since last inspection.
Properly reinstall a flow meter (10x pipe diameter in straight pipe length upstream from the flow meter and 5x pipe diameter in length of straigh pipe after flow meter) or have a pump curve available for water pump used for the pool.


Inspection Information


[?] Facility Type: Pool

[?] Inspection Type: Standard

[?] Inspection Date: 14-June-2018

Comments
No other violations noted at this time.
Water clarity, disinfectant residuals, and water quality readings meet minimum code requirements at this time.
Signage and safety equipment provided as required.
Restrooms are clean and properly supplied.
Pool looks really good at this time. Keep up the good work!