Sampling Details | |||
---|---|---|---|
Sub Type: Other | Special Feature: | Location: | |
Area: 1160 | Volume (gallons): 35500 | Flow measure reading (gpm): 110 | Minimum required flow (gpm): 74 |
Disinfectant: Sodium Hypochlorite | Secondary Disinfectant: | ORP: 735 | Turnover Rate (min): 480 |
Total Chlorine (ppm): 3 | Free Chlorine (ppm): 3 | Combined Chlorine (ppm): 0 | Total Bromine (ppm): |
Alkalinity (ppm): 120 | Pool water temp ˚F: 76 | pH: 7.7 | Cyanuric acid (ppm): |
Spa water temp ˚F: | Spa water replaced every 30 days: | Max Allow. Filter Flow (gpm): 141 | Max Allow. Flow: Jet pump capacity (gpm): |
Max Allow. Flow: SF pump capacity (gpm): |
3701-31-04 (D)(7)(d) / Flow or pressure switch with a shut off valve shall be provided and tested monthly.
Critical Repeat ACC unit alarm testing is not documented. Test, then record ACC unit testing at least every month.
Have the ACC unit serviced or replaced with a unit that has a flow or pressure switch with an automatic shut off valve. Provide records indicating that the unit is being tested monthly. Correct By: 12-Jun-2019
3701-31-04 (E)(2)(e) / Working emergency telephone/call box provided.
Repeat A phone could not be located. Provide a phone for use in the case of an emergency.
Ensure that the emergency device is functioning properly and rings to the emergency response authorities. Correct By: 12-Jun-2019
Comments |
---|
Pool Notes: 1. The pool water is clear. 2. ACC unit pH noted at 7.8. 3. Pool turnover rate=5.4 hours. 4. Filter pressure gauge noted at 15psi. 5. The pool pH was between 7.6 and 7.8. 6. ACC unit alarm functions when tested. 7. The report was emailed to Ms. Butts. Contact Scott Bradley,R.S. (732-7614) with any questions |