Sampling Details | |||
---|---|---|---|
Sub Type: Wading Pool | Special Feature: | Location: | |
Area: 136 | Volume (gallons): 1530 | Flow measure reading (gpm): | Minimum required flow (gpm): |
Disinfectant: Sodium Hypochlorite | Secondary Disinfectant: | ORP: 200 | Turnover Rate (min): |
Total Chlorine (ppm): 0 | Free Chlorine (ppm): 0 | Combined Chlorine (ppm): 0 | Total Bromine (ppm): |
Alkalinity (ppm): | Pool water temp ˚F: | pH: | Cyanuric acid (ppm): |
Spa water temp ˚F: | Spa water replaced every 30 days: | Max Allow. Filter Flow (gpm): | Max Allow. Flow: Jet pump capacity (gpm): |
Max Allow. Flow: SF pump capacity (gpm): |
3701-31-04 (B)(4)(a)(ii) / Combined chlorine is tested daily at pool side prior to use
No record for 8/11 was filled out by operators inspection at 11:30. Combined chlorine was not tested daily at pool side prior to use.
Test for combined chlorine prior to bathers entering the water and If ACC is in use combined chlorine must be tested every 12 hours while the pool is in use. 3701-31-04 (B)(4)(a)(vi) / Total alkalinity is tested weekly
Repeat Total alkalinity was not tested weekly.
Test total alkalinity at least once/week. 3701-31-04 (C)(2) / pH is within 7.2 to 7.8
Repeat pH was outside the range of 7.2 to 7.8.
Treat the pool water so that the pH is within the acceptable range.
The following violation(s) have been corrected since the last inspection. |
---|
3701-31-04 ( D )(6)(a)/ORP reading shall be 650 millivolts or greater. ORP reading was below 650 mv Have the ACC unit inspected to determined why the ORP is low. |
3701-31-04 (B)(1)(c)/Minimum disinfection residual shall be maintained as required. Chlorine disinfectant residual was less than 1 ppm for the pool Do not operate the pool when the disinfectant residuals are less than what is required. Ensure the chlorine disinfectant residual is at 1 ppm or above prior to placing the pool back into operation. |
3701-31-04(D)(6)(a)(2)/Pool free chlorine disinfectant residual shall be above 1 ppm. Pool free chlorine disinfectant residual was below 1 ppm. Do not operate the pool until the chlorine disinfectant residual is at 1 ppm or above. |
Comments |
---|
-Pool was open and no one had visited or recorded water quality for both main and wading pool. - Operator arrived at time of inspection to increase chlorine levels. ORP was brought up to 650 and chlorine levels were noted at 1ppm. Re-inspection to confirm baby pool can maintain 1ppm chlorine and ORP is above 650. |