Sampling Details | |||
---|---|---|---|
Sub Type: Other | Special Feature: | Location: | |
Area: 1800 | Volume (gallons): 54000 | Flow measure reading (gpm): 115 | Minimum required flow (gpm): 113 |
Disinfectant: Sodium Hypochlorite | Secondary Disinfectant: | ORP: 752 | Turnover Rate (min): 480 |
Total Chlorine (ppm): 4 | Free Chlorine (ppm): 4 | Combined Chlorine (ppm): 0 | Total Bromine (ppm): |
Alkalinity (ppm): 100 | Pool water temp ˚F: 81 | pH: 7.3 | Cyanuric acid (ppm): |
Spa water temp ˚F: | Spa water replaced every 30 days: | Max Allow. Filter Flow (gpm): 74 | Max Allow. Flow: Jet pump capacity (gpm): |
Max Allow. Flow: SF pump capacity (gpm): |
3701-31-04 (B)(1)(a) / Outlet covers shall be installed/secured/in compliance
Critical Repeat Specifications for the one (1) main drain cover has not been provided to CCPH.
Provide specifications (Install/Replacement Dates) for the main drain cover to verify VGB compliance. 3701-31-04 (B)(6) / Equipment is maintained per manufacturers specifications.
Repeat A pressure gauge on one of the filters is not working.
Repair the gauge so filter pressures can be monitored. 3701-31-04 (B)(6)(k) / Outlet drain covers are secure/meet ANSI/ASME A112.19.8-2007 requirements.
Critical Repeat Specifications for the one (1) one main drain cover has not been provided to CCPH.
Provide specifications (Install/Replacement Dates) for the main drain cover to verify VGB compliance. 3701-31-04 (B)(6)(q) / Depth markers/deck warning signs are maintained
Repeat Depth markers are not clearly legible.
By the beginning of the 2018 Pool Season, all depth markers must be clearly visible. 3701-31-04 (D)(8) / Acceptable test kit provided/adequate/in good repair
Solutions for testing free chlorine were not available.
Provide the testing solutions (Solutions 1&2) to test for free chlorine.
Comments |
---|
No other violations observed during the inspection. The pool otherwise looks great! Pool Notes: 1. The 2017 pool license is posted. 2. The pool water is clear. 3. Proper safety equipment is available for use. 4. ACC unit and SVRS device testing is documented in the pool records. 5. Working filter pressure gauge was noted at 56psi. Due to the high pressure, it is recommended the filter be back washed. 6. Pool turnover rate=7.8 hours. 7. The pool pH was between 7.2-7.4 8. The report was emailed to Ms. Michelson. Inspection conducted by Scott Bradley,R.S. 732-7614 |