Sampling Details
Sub Type: Hotel/motel Special Feature: Location:
Area: 418 Volume (gallons): 12500 Flow measure reading (gpm): 40 Minimum required flow (gpm): 26
Disinfectant: Salt Secondary Disinfectant: ORP: 195 Turnover Rate (min): 312
Total Chlorine (ppm): 0 Free Chlorine (ppm): 0 Combined Chlorine (ppm): 0 Total Bromine (ppm):
Alkalinity (ppm): 60 Pool water temp ˚F: 74 pH: 7.9 Cyanuric acid (ppm):
Spa water temp ˚F: Spa water replaced every 30 days: Max Allow. Filter Flow (gpm): Max Allow. Flow: Jet pump capacity (gpm):
Max Allow. Flow: SF pump capacity (gpm):
[?] A summary of the violations found during the inspection are listed below.

3701-31-04 ( D )(6)(a) / ORP reading shall be 650 millivolts or greater.
ORP reading was below 650 mv. ORP noted at 195.
Have the ACC unit inspected to determined why the ORP is low.
3701-31-04 (B)(4) / The licensee /authorized representative is keeping records
Repeat The licensee /authorized representative was not keeping or maintaining operational records. Records were not found for week in which inspection took place.
All facility records must be maintained and available for review upon request. Ensure that records are retained for a minimum of two years for review.
3701-31-04 (B)(6) / Equipment is maintained per manufacturers specifications.
Equipment was not maintained per manufacturers specifications. Missing skimmer weirs.
All equipment must be maintained in accordance with the manufacturers specifications.
3701-31-04 (B)(6)(o) / Ladders/stairs/steps are in good repair/slip resistent
Ladders/stairs/steps were not in good repair or were not slip resistant. Observed ladder in deep end of pool to be loose.
Repair or replace the ladders/stairs/steps so that they are slip resistant and in good repair.
3701-31-04 (B)(6)(y) / Chemicals are properly stored/used
Critical Chemical containers were stored without labels identifying the contents. Observed acids stored over bases in storage room.
Label and properly store all chemical containers to avoid a chemical reaction or unnecessary exposure.
3701-31-04 (D)(7)(d) / Flow or pressure switch with a shut off valve shall be provided and tested monthly.
Critical Flow or pressure switch for a shut off valve was not provided or the unit was not tested monthly
Have the ACC unit serviced or replaced with a unit that has a flow or pressure switch with an automatic shut off valve. Provide records indicating that the unit is being tested monthly.
3701-31-04 (E)(2)(d) / First aid kit provided
Repeat First aid equipment was not provided.
Provide first aid equipment, including a first aid kit, at the pool at all times. Ensure first aid kit is stocked with gloves.
3701-31-04(D)(6)(a)(2) / Pool free chlorine disinfectant residual shall be above 1 ppm.
Critical Repeat Pool free chlorine disinfectant residual was noted at 0 ppm.
Do not operate the pool until the chlorine disinfectant residual is at 1 ppm or above.


Inspection Information


[?] Facility Type: Pool

[?] Inspection Type: Standard

[?] Inspection Date: 22-December-2022

Comments
Inspection Notes:

1. Pool clear with good visibility.
2. Emergency phone in operation & proper signage posted.
3. Gloves should be restocked in First Aid Kit.
4. Ensure skimmer weirs are in place.
5. Ensure chlorine is above 1ppm. Re-Inspection will be required.