Sampling Details
Sub Type: Other Special Feature: Location:
Area: 1325 Volume (gallons): 39750 Flow measure reading (gpm): Minimum required flow (gpm): 83
Disinfectant: Sodium Hypochlorite Secondary Disinfectant: ORP: 720 Turnover Rate (min): 480
Total Chlorine (ppm): 1 Free Chlorine (ppm): 1 Combined Chlorine (ppm): 0 Total Bromine (ppm):
Alkalinity (ppm): 70 Pool water temp ˚F: 76 pH: 7.2 Cyanuric acid (ppm):
Spa water temp ˚F: Spa water replaced every 30 days: Max Allow. Filter Flow (gpm): 141 Max Allow. Flow: Jet pump capacity (gpm):
Max Allow. Flow: SF pump capacity (gpm):
[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (B)(6)(i) / A means of determining rate-of-flow on all water pumps
A means of determining rate-of-flow was not found for all water pumps. Observed the flow meter to be stuck. Unable to record flow to calculate required turnover rate.
Properly install a flow meter or have a pump curve available for every water pump used for the pool. Will follow-up at next standard inspection.


Inspection Information


[?] Facility Type: Pool

[?] Inspection Type: Standard

[?] Inspection Date: 15-August-2022

Comments
--Per information on file, pool main drain covers were due to be replaced in 2021. Replace main drain cover and submit certificates of compliance, make/model information along with expiration dates. In the alternative, submit updated information on drain covers indicated that they have been replaced.
--Free chlorine was at required minimum. Recommend increasing the free chlorine to 2-4 ppm.