Sampling Details
Sub Type: Apartment/Condo Special Feature: Location:
Area: 1615 Volume (gallons): 63447 Flow measure reading (gpm): Minimum required flow (gpm):
Disinfectant: Sodium Hypochlorite Secondary Disinfectant: ORP: Turnover Rate (min):
Total Chlorine (ppm): 2 Free Chlorine (ppm): 2 Combined Chlorine (ppm): 0 Total Bromine (ppm): 0
Alkalinity (ppm): Pool water temp ˚F: pH: Cyanuric acid (ppm):
Spa water temp ˚F: Spa water replaced every 30 days: Max Allow. Filter Flow (gpm): Max Allow. Flow: Jet pump capacity (gpm):
Max Allow. Flow: SF pump capacity (gpm):
[?] A summary of the violations found during the inspection are listed below.

3701-31-04 ( D )(6)(a) / ORP reading shall be 650 millivolts or greater.
Repeat ORP reading was below 650 mv, Observed at 550.
Have the ACC unit inspected to determined why the ORP is low.
3701-31-04 (B)(1)(c) / Minimum disinfection residual shall be maintained as required.
Critical Repeat Chlorine disinfectant residual was less than 1 ppm for the pool, 0.2 ppm. A reinspection is necessary. Facility voluntarily closed pool.
Do not operate the pool when the disinfectant residuals are less than what is required. Ensure the chlorine disinfectant residual is at 1 ppm or above prior to placing the pool back into operation.
3701-31-04 (B)(4)(a)(vi) / Total alkalinity is tested weekly
Repeat Total alkalinity was not tested weekly.
Test total alkalinity at least once/week.
3701-31-04 (B)(4)(c) / SVRS/APSOS/ACC test results/ service records are maintained
Repeat SVRS/APSOS/ACC test results/ service records were not maintained. Ensure to test and record the ACC and Stingle switch monthly.
The test results/service records for these devices must be kept on site for review. If the device has not been recently serviced, have the device tested immediately and provide documentation of the test results.
3701-31-04 (B)(6)(s) / Perimeter barrier is in good repair to prevent unauthorized entry
Repeat Gates or doors were not self-closing and lockable. Pool voluntarily closed.
Repair gates or doors in order to be self-closing and lockable.
3701-31-04(D)(6)(a)(2) / Pool free chlorine disinfectant residual shall be above 1 ppm.
Critical Repeat Pool free chlorine disinfectant residual was below 1 ppm. Observed at 0.2. Pool voluntarily closed. Reinspection necessary.
Do not operate the pool until the chlorine disinfectant residual is at 1 ppm or above.


Inspection Information


[?] Facility Type: Pool

[?] Inspection Type: Follow-up

[?] Inspection Date: 26-August-2019

The following violation(s) have been corrected since the last inspection.
Comments
Reinspection notes:
-Gate was not self closing, not enough tension. Ensure gate is self closing and self latching at all times. Reinspection necessary.