Sampling Details | |||
---|---|---|---|
Sub Type: Other | Special Feature: | Location: | |
Area: 3200 | Volume (gallons): 137500 | Flow measure reading (gpm): 375 | Minimum required flow (gpm): 287 |
Disinfectant: Sodium Hypochlorite | Secondary Disinfectant: | ORP: | Turnover Rate (min): 480 |
Total Chlorine (ppm): 7 | Free Chlorine (ppm): 7 | Combined Chlorine (ppm): 0 | Total Bromine (ppm): |
Alkalinity (ppm): 80 | Pool water temp ˚F: 79 | pH: 7.0 | Cyanuric acid (ppm): 0 |
Spa water temp ˚F: | Spa water replaced every 30 days: | Max Allow. Filter Flow (gpm): 106 | Max Allow. Flow: Jet pump capacity (gpm): |
Max Allow. Flow: SF pump capacity (gpm): |
3701-31-04 (B)(6)(k) / Outlet drain covers are secure/meet ANSI/ASME A112.19.8-2007 requirements.
Critical Equalizer lines were not plugged at the time of the inspection.
Plug the equalizer lines as required. Equalizer lines must either be plugged with VGB compliant covers at the pool wall or plugged inside the skimmer housing or otherwise removed from the pool. 3701-31-04 (B)(6)(q) / Depth markers/deck warning signs are maintained
Depth markers/deck warning signs were not maintained in a clearly legible/visible manner. There are no depth markers or No Diving signs on the pool deck as required.
Replace the depth markers/deck warning signs so that bathers are able to clearly see the depth of the water and that no diving is permitted where clearly indicated. Markers / warning signs must be placed on top of the deck, within 2 feetof the water's edge, and not more than 25 lineal feet apart. Depth must be expressed in feet and inches (to the nearest 6-inch mark), with numbers at least 4 inches in size in a color that contrasts with the background. 3701-31-04 (B)(6)(s) / Perimeter barrier is in good repair to prevent unauthorized entry
Entry gate was propped open at the start of the inspection.
Self-closing and self-latching gate must not be propped open.
Comments |
---|
Water clarity, disinfectant residuals, and water quality readings meet minimum code requirements at this time. Lifeguards are on duty as required. Certifications were checked during inspection. All lifeguard certifications are current. Unless otherwise noted in this report, signage and safety equipment provided as required. |