Sampling Details | |||
---|---|---|---|
Sub Type: Apartment/Condo | Special Feature: | Location: | |
Area: 1500 | Volume (gallons): 42374 | Flow measure reading (gpm): 90 | Minimum required flow (gpm): 88 |
Disinfectant: Sodium Hypochlorite | Secondary Disinfectant: | ORP: | Turnover Rate (min): |
Total Chlorine (ppm): 0.4 | Free Chlorine (ppm): 0.2 | Combined Chlorine (ppm): 0.2 | Total Bromine (ppm): |
Alkalinity (ppm): 90 | Pool water temp ˚F: 82 | pH: 7.8 | Cyanuric acid (ppm): 0 |
Spa water temp ˚F: | Spa water replaced every 30 days: | Max Allow. Filter Flow (gpm): | Max Allow. Flow: Jet pump capacity (gpm): |
Max Allow. Flow: SF pump capacity (gpm): |
3701-31-04 (B)(1)(c) / Minimum disinfection residual shall be maintained as required.
Critical Repeat Corrected During Inspection Chlorine disinfectant residual was less than 1 ppm for the pool
Do not operate the pool when the disinfectant residuals are less than what is required. Ensure the chlorine disinfectant residual is at 1 ppm or above prior to placing the pool back into operation. 3701-31-04 (B)(4)(a)(iv) / Water temperatures are recorded daily
Repeat Water temperatures were not being recorded daily.
Take and record the water temperature at least once/day. 3701-31-04(D)(6)(a)(2) / Pool free chlorine disinfectant residual shall be above 1 ppm.
Critical Repeat Corrected During Inspection Pool free chlorine disinfectant residual was below 1 ppm.
Do not operate the pool until the chlorine disinfectant residual is at 1 ppm or above.
Comments |
---|
Pool water is clear. Perimeter barrier is secure. Safety equipment is provided. Appropriate warning signs are posted. Pool looks good! Keep up the good work! |