Sampling Details | |||
---|---|---|---|
Sub Type: Wading Pool | Special Feature: | Location: | |
Area: 225 | Volume (gallons): 2531 | Flow measure reading (gpm): 50 | Minimum required flow (gpm): 21 |
Disinfectant: Sodium Hypochlorite | Secondary Disinfectant: | ORP: 640 | Turnover Rate (min): 50 |
Total Chlorine (ppm): 3 | Free Chlorine (ppm): 3 | Combined Chlorine (ppm): 0 | Total Bromine (ppm): |
Alkalinity (ppm): 70 | Pool water temp ˚F: 82 | pH: 7.3 | Cyanuric acid (ppm): |
Spa water temp ˚F: | Spa water replaced every 30 days: | Max Allow. Filter Flow (gpm): | Max Allow. Flow: Jet pump capacity (gpm): |
Max Allow. Flow: SF pump capacity (gpm): |
3701-31-04 ( D )(6)(a) / ORP reading shall be 650 millivolts or greater.
ORP reading was below 650 mv, noted at 640.
Have the ACC unit inspected to determined why the ORP is low. 3701-31-04 (B)(1)(a) / Outlet covers shall be installed/secured/in compliance
Critical Equalizer line was not plugged.
Equalizer line must have a VGB cover to avoid hair/body entrapment. If no VBG covers are provided, the equilizer line must be disabled by plugging the equalizer line under skimmer basket (not the line to the pump.)
Comments |
---|
Notes: -Pool water was clear. -Disinfectant residuals meet minimum code requirements at this time. -Safety equipment was provided. -Re-inspection for equalizer line. |