Sampling Details
Sub Type: School Special Feature: Location:
Area: 1800 Volume (gallons): 65000 Flow measure reading (gpm): 0 Minimum required flow (gpm): 135
Disinfectant: Calcium Hypochlorite Secondary Disinfectant: ORP: 650 Turnover Rate (min): 480
Total Chlorine (ppm): 6 Free Chlorine (ppm): 6 Combined Chlorine (ppm): 0 Total Bromine (ppm):
Alkalinity (ppm): 110 Pool water temp ˚F: 87 pH: 7.3 Cyanuric acid (ppm): 0
Spa water temp ˚F: Spa water replaced every 30 days: Max Allow. Filter Flow (gpm): Max Allow. Flow: Jet pump capacity (gpm):
Max Allow. Flow: SF pump capacity (gpm):
[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (A) / All construction or alterations of a public swimming pool are approved
A new disinfection system was installed. Facility has converted from trichlor to calcium hypochlorite to eliminate high cyanuric acid readings. Change must be submitted to the Ohio Dept. of Health for approval on the Equipment Replacement Notification Report (ERNR) provided during this inspection.
Change must be submitted to the Ohio Dept. of Health for review and approval on the Equipment Replacement Notification Report (ERNR) provided during this inspection.
3701-31-04 (C)(3) / Total alkalinity is at or greater than 60 ppm
Repeat Corrected During Inspection The initial total alkalinity reading of 30 ppm was less than minimum required alkalinity of 60 ppm.
Add approximately 63 lbs. of sodium bicarbonate to raise the total alkalinity to at least 60 ppm. Sodium bicarbonate was added when bathers were not in the pool. Second test: 110 ppm.


Inspection Information


[?] Facility Type: Pool

[?] Inspection Type: Standard

[?] Inspection Date: 06-November-2015

Comments
Facility inspection notes:
Water clarity is sufficient.
Disinfectant residual and pH readings meet code requirements at this time.
Signage and safety equipment provided as required.