Sampling Details
Sub Type: Other Special Feature: Location:
Area: 1800 Volume (gallons): 54000 Flow measure reading (gpm): 120 Minimum required flow (gpm): 113
Disinfectant: Sodium Hypochlorite Secondary Disinfectant: ORP: 688 Turnover Rate (min): 480
Total Chlorine (ppm): 3 Free Chlorine (ppm): 3 Combined Chlorine (ppm): 0 Total Bromine (ppm):
Alkalinity (ppm): 80 Pool water temp ˚F: 80 pH: 7.6 Cyanuric acid (ppm):
Spa water temp ˚F: Spa water replaced every 30 days: Max Allow. Filter Flow (gpm): 74 Max Allow. Flow: Jet pump capacity (gpm):
Max Allow. Flow: SF pump capacity (gpm):
[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (B)(1)(a) / Outlet covers shall be installed/secured/in compliance
Critical Repeat Specifications for the one (1) main drain cover could not be located.
Provide specifications for the main drain cover to verify VGB compliance.
3701-31-04 (B)(6)(k) / Outlet drain covers are secure/meet ANSI/ASME A112.19.8-2007 requirements.
Critical Repeat Specifications for the one (1) main drain cover could not be located.
Provide specifications for the main drain cover to verify VGB compliance.
3701-31-04 (B)(6)(q) / Depth markers/deck warning signs are maintained
Repeat The pool deck depth markers have faded.
Repaint the faded pool deck depth markers.


Inspection Information


[?] Facility Type: Pool

[?] Inspection Type: Standard

[?] Inspection Date: 08-August-2018

Comments
No other violations observed during the inspection.
The pool otherwise looks great!
Pool Notes:
1. The 2018 pool license is posted.
2. The pool water is clear.
3. Proper safety equipment is available for use.
4. ACC unit and SVRS device testing is documented in the pool records.
5. Pool turnover rate=7.5 hours.
6. ACC unit pH noted at 7.5.
7. Filter pressure gauges noted at 8 and 9psi.
8. The report was emailed to Ms. Michelson.
Inspection conducted by Scott Bradley,R.S. 732-7614