Sampling Details
Sub Type: Other Special Feature: Location:
Area: 1800 Volume (gallons): 54000 Flow measure reading (gpm): 120 Minimum required flow (gpm): 113
Disinfectant: Sodium Hypochlorite Secondary Disinfectant: ORP: 688 Turnover Rate (min): 480
Total Chlorine (ppm): 4 Free Chlorine (ppm): 4 Combined Chlorine (ppm): 0 Total Bromine (ppm):
Alkalinity (ppm): 100 Pool water temp ˚F: 83 pH: 7.5 Cyanuric acid (ppm):
Spa water temp ˚F: Spa water replaced every 30 days: Max Allow. Filter Flow (gpm): 74 Max Allow. Flow: Jet pump capacity (gpm):
Max Allow. Flow: SF pump capacity (gpm):
[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (B)(6) / Equipment is maintained per manufacturers specifications.
The filter pressure gauges are not working.
Repair the gauges so filter pressures can be monitored.
3701-31-04 (B)(6)(k) / Outlet drain covers are secure/meet ANSI/ASME A112.19.8-2007 requirements.
Critical Specifications for the two (2) main drain covers have not been provided.
Provide specifications for the main drain covers to verify VGB compliance.


Inspection Information


[?] Facility Type: Pool

[?] Inspection Type: Standard

[?] Inspection Date: 24-June-2015

Comments
No other violations observed during the inspection.
The pool otherwise looks great!
Pool Notes:
1. The 2015 pool license is posted.
2. The pool water is clear.
3. Proper safety equipment is available for use.
4. ACC unit pH noted at 7.5.
5. Pool turnover rate=7.5 hours.
6. The pool pH was between 7.4-7.6.
7. Prior to the start of the 2016 Pool Season, the facility may want to consider repainting the pool deck "No Diving" signage and depth markers.
8. Copy of the report was left with the pool records.
Inspection conducted by Scott Bradley,R.S. 732-7614